国产精品多人P群无码,国产亚洲人成在线播放,日韩高清无码一区二区 ,国产精品无码一区二区三区太

Hello, welcome to Jiaozuo City, Hong Kun cathodic protection corrosion Material Co., Ltd. website!
Service| Contact us| Chinese| English
tel
Search keyword:Sacrificial anode Plus currentPackage product

Plus current series

Home > Products > Plus current series
Ground Resistance Tester
產(chǎn)品大圖
  • Ground Resistance Tester
Product description

  ZC-8 grounding resistance tester use and scope of application:

  ZC-8 grounding resistance tester for direct measurement of a variety of grounding device grounding resistance, but also for the general low-resistance measurement, four-button (0 ~ 1 ~ 10 ~ 100Ω specifications) can also measure the soil resistivity.

  ZC-8 grounding resistance tester main specifications and range as follows:

  Specification range Minimum qualified value

  1-10-100 0 ~ 1Ω 0.01

  0 ~ 10 0.1

  0 ~ 100 1

  10-100-100 0 to 10 0.1

  0 ~ 100 1

  0 ~ 1000 10

  ZC-8 grounding resistance tester technical parameters:

  1. This product complies with GB7676-98 direct role simulation instructions electrical measuring instruments and accessories definition and general requirements and ZBN21012 grounding resistance table professional standards of the relevant provisions.

  2. The reference value of the instrument is range.

  3. The basic error of the instrument is a percentage of the reference value indicating that the limit of its basic error is ± 3% of the range.

  4. Instrument working environment temperature -20 ~ +50 ℃.

  5. Instrument due to temperature changes caused by changes in instructions, converted to 10 ℃ per change is not greater than the basic error.

  6. Instrument work environment humidity of 25% to 95%, resulting in changes in the indication value is not greater than the basic error.

  7. The instrument work position is horizontal.

  8. The instrument is tilted by 5 ° in either direction from the horizontal working position, thereby causing the indication value to change no more than 1/2 of the basic error.

  9. The instrument under the influence of the external magnetic field strength of 0.4KA / m caused by the indication value of the change is not greater than 1.5% of the reference value.

  10. Insulation resistance between instrument line and housing is not less than 20MΩ.

  11. The voltage test of the instrument line and the housing is 500V.

  12. The protective performance of the enclosure is splashproof.

  13. The grounding resistance of the auxiliary probe does not affect the measurement when its resistance is not greater than the value specified in the table below.

  14. Instrument generator handle rated speed of 120r / min.

  Range Rp Rc

  0 ~ 1Ω 500Ω

  0 ~ 10Ω 1000Ω

  0 ~ 100Ω 2000Ω

  0 ~ 1000Ω 5000Ω


Order online

Hong Kun anti-corrosion remind you: In order to timely contact with you, please be sure to fill out your contact information and demand information, you can enter your needs, such as the type of raw materials, capacity, feed size, The final product size, etc .; you can also contact us through the 24-hour online customer service, Hong Kun anti-corrosion - to become your satisfaction partner.

Products name:
Name:
Tel:
Address:
Notes:
Verification code: